70,550#/Hour 565 PSI Walchandnagar Bagasse Fired Bi-Drum Water Tube Boiler
Stock #RG8882
Used bagasse fired bi-drum water tube boiler made by Walchandnagar Industries limited in 1988. Main characteristics as follows: - maximum continuous rating is 32 tph (70,550 PPH), peak rating 35.2 tph (77,600 PPH). - steam pressure at oultet of main stream stop valve is 32 kg/cm2 (31.38 bar or 455 psi), design pressure is 40 kg/cm2 (39.23 bar or 570 psi). - final steam temperature 380 degrees Celsius +/- 15 degrees. - hydraulic test pressure 60 kg/cm2 (58.84 bar or 850 psi). - feed water temperature at economizer inlet 85 degrees Celsius. - type of grate : traveling. - ash disharge : bottom. - grate drive mechanism : hydraulic drive. - heating surface: furnace 265 M2, boiler bank 720 M2, super heater 131 M2, economizer 359.52 M2, air preheater 850 M2. Quotes will be for (1) boiler, but (2) are available.Location : Asia
Ask for price of 70,550#/Hour 565 PSI Walchandnagar Bagasse Fired Bi-Drum Water Tube Boiler